MATERIAL STANDARD
1. GENERAL
WIRING
- The
wiring plan will be installed per requirements of these
specifications utilizing materials meeting all
applicable ANSI/TIA/EIA standards.
-
Materials will be as listed or will be equivalent
products of other manufacturers meeting the intent and
quality level of the ANSI/TIA/EIA TSB36 and TSB40
specifications.
- All
installed wire will be tested "100 percent good" after
installation by
Connect Technologies.
- All
products will be new and brought to the job site in
original manufacturer's packaging. Electrical components
(including innerduct) will bear the Underwriters
Laboratories label. All communications cable will bear
flammability testing ratings as follows:
-
Initial cable inspection:
Connect Technologies will
inspect all cable prior to installation to verify that
it is identified properly on the reel identification
label, that it is of proper gauge, containing the
correct number of pairs, etc. Note any buckling of the
jacket that would indicate possible problems. Damaged
cable or any other components failing to meet
specifications will not be used in the installation.
2. STATION
WIRING
- The
wire provided for all outlets will be one four-pair UTP,
Category 5E cable per jack.
- Duplex
data outlet will have two data cables each with a jack
(if required).
-
Telephone/data outlet will have one voice cable and jack
and one data cable and jack (if required).
- The
Category 5E four-pair UTP cable is UL performance level
tested.
3. STATION
HARDWARE
-
Flush-mounted jacks will be high-quality Category 5E
RJ45 modular jacks with circuit board construction and
IDC-style or 110-style wire, T568B terminations. Jacks
will meet ANSI/TIA/EIA TSB40 recommendations for
Category 5E connecting hardware.
-
Faceplates will match manufacturer for RJ45 outlets at
all locations.
4. DATA MDF/IDF
TERMINATION HARDWARE
- New
data Category 5E termination hardware: The Category 5E
data station cable will be terminated on Category 5E
RJ45 patch panels with circuit board construction in all
IDF/MDF locations. The RJ45 patch panels will be rack
mounted with cable management panels per communication
detail sheets. All wall brackets, patch panels, and
cable management panels for all IDF/MDF layouts and
equipment rack configurations will be done by
Connect Technologies.
- Wall
brackets will be provided for all patch panels and cable
management panels for wall mount applications.
- Cable
management panels will have five (5) D-rings for wire
distribution with a minimum panel dimension of 3½" x
19".
|